Speak to one of our experts.
A rack/tower UPS with line interactive topology, the CyberPower Smart App CPS1500AVR provides battery backup (using simulated sine wave output) and surge protection for department servers, workgroup servers, workstations, network devices, and telecom installations without active PFC power supplies. The CPS1500AVR uses Automatic Voltage Regulation (AVR) to correct minor power fluctuations without switching to battery power, which extends battery life. AVR is essential in areas where power fluctuations occur frequently. The CPS1500AVR comes with a three-year warranty and a $300,000 Connected Equipment Guarantee.
(a) UPS unit, User manual, Rack mount brackets, Telephone cable, PowerPanel® Business Edition software Download Card, Serial interface cable (DB-9), USB A+B type cable, Warranty registration card.
PowerPanel Business software download available here.
WARNING:
This product can expose you to chemicals including Styrene, which are known to the State of California to cause cancer, and Bisphenol A (BPA), which are known to the State of California to cause birth defects or other reproductive harm.
General | |
UPS Topology | Line Interactive |
Energy Saving | GreenPower UPS™ Bypass |
Input | |
Voltage | Nominal 120V |
Input voltage range | 90Vac – 140Vac |
Frequency | 47-63 Hz |
Plug Type | NEMA 5-15P |
Plug Style | Right Angle, 45° Offset Right |
Cord Length (FT) | 10 ft |
Output | |
VA | 1500 |
Watts | 900 |
Automatic Voltage Regulation | Yes – Single Boost (11.5%) |
On Battery Voltage | 120Vac ± 10% |
On Battery Frequency | 50/60Hz ± 1% |
On Battery Waveform | Simulated Sine Wave |
Outlet Type | NEMA 5-15R |
Outlets – Total | 8 |
Outlets – Battery & Surge Protected | 8 |
Overload Protection | Internal circuitry limiting / circuit breaker |
Transfer Time | 4 ms |
Battery | |
Runtime at Half Load | 18 minutes |
Runtime at Full Load | 7 minutes |
Battery Voltage | 12V |
Battery Capacity | 7Ah |
User Replaceable | Yes |
Hot Swappable | Yes |
Typical Recharge Time | 8 hours |
Replacement Battery | RB1270X4F RB1270X4E (With serial numbers beginning with ‘BB’) |
Battery Quantity | 4 |
Surge Protection & Filtering | |
Surge Suppression | 1,840 J |
EMI/RFI Filtering | Yes |
RJ11/RJ45 | 1-In, 1-Out (Combo 10/100) |
Coax Protection | 1-In, 1-Out |
Management & Communications | |
LCD Interface | No |
HID Compliant USB Port | Yes |
Serial Port | Yes (2x) (Dry Contact) |
LED Indicators | Load Level Battery Level Power On Online Using Battery Replace Battery AVR Mute Overload Fault Wiring Fault |
Audible Alarms | On Battery Low Battery Overload |
Battery Missing, Fault | |
Software (Free Download) | PowerPanel Business Edition |
SNMP / HTTP Remote Monitoring | Yes, with optional RMCARD205 |
Physical | |
Form Factor | Rack/Tower |
Dimensions (WxHxD) (inch) | 17.25 × 3.50 × 15.75 |
Weight (lb) | 50.50 |
Shipping Dimensions (WxHxD) (inch) | 21.34 × 11.81 × 20.47 |
Shipping Weight (lb) | 53.70 |
Environmental | |
Operating Temperature | 32 °F to 104 °F / 0 °C to 40 °C |
Operating Relative Humidity | 0% – 90% (non-condensing) |
Operating Elevation | 10,000 ft / 3,000 m |
Storage Temperature | 5°F to 113°F / -15°C to 45 °C |
Storage Relative Humidity | 0% – 95% non-condensing |
Storage Elevation | 50,000 ft / 15,000 m |
Certifications | |
Safety | UL1778, cUL 107.1, FCC Cl B |
Warranty | |
Product Warranty | 3 Years Limited |
Connected Equipment Guarantee | Lifetime |
CEG Amount | $300,000 |
The Smart App Series offers full-featured network UPS management capabilities with the PowerPanel® Business Edition software and an optional SNMP network management card. These remote management tools enable centralized power management, monitoring, control, and configuration. They also provide for safe shutdown of connected servers, workstations, and other devices via a standard Web browser or network management system (NMS).
Safe Shutdown
The PowerPanel® Business Edition software, included with every Smart App Sinewave UPS, enables an administrator to remotely manage each aspect of the UPS and facilitate the orderly automatic shutdown of connected equipment in the event of an extended power outage. This software also provides comprehensive network power management for corporate servers and critical workstations supported by the UPS, such as application/operating system shutdown, event logging, reporting, alerts and notifications.
Programmable Outlet Control
Smart App UPS systems allow programming of critical outlets and non-critical outlets, giving administrators the ability to prioritize outlets and increase battery backup runtimes for the most critical equipment during extended power outages. Programmable outlet control also gives an administrator the option to delay-start non-critical outlets, permitting the internal batteries to fully recharge more quickly. This feature is vital to data centers where seamless, uninterrupted equipment bootup is a necessity.
Automatic Voltage Regulation (AVR) in line interactive UPS systems stabilizes the incoming AC signal to maintain output power at a nominal 120 volts by controlling high and low voltages without resorting to battery power. This significantly increases battery life and lessens the likelihood of data loss, memory freezes, and system crashes.
How AVR Works in a Line Interactive UPS
A line interactive UPS includes an AVR autotransformer a special type of transformer designed to switch between powered coils of wire in response to variances in utility power input, thereby increasing or decreasing the magnetic field and the resulting output voltage to connected equipment.
This type of UPS tolerates undervoltage brownouts and overvoltage surges without consuming backup battery power by automatically selecting different power taps on the AVR autotransformer. During normal operation, incoming AC power bypasses the autotransformer (where voltage highs and lows are controlled) while also charging the battery. When the incoming voltage falls below the AVR range, the UPS switches to battery backup, and the DC-AC inverter circuitry is engaged. Power will continue to be supplied by the battery-inverter circuit until incoming voltage returns to the range manageable by the AVR.